Status: UP Framing: ESF Encoding: B8ZS PCM: u-law
Receive Level: +2dB to -7.5dB
Alarms Violations
----------------------------- -----------------------------
Blue 0 Bipolar 0
Yellow 1 CRC Errors 0
Receive Carrier Loss 0 Multiframe Sync 0
Loss of Sync 0
A show line0 for the second Portmaster
---------------------- line0 - T1 Primary Rate ISDN ---------------
Status: UP Framing: ESF Encoding: B8ZS PCM: u-law
Receive Level: +2dB to -7.5dB
Alarms Violations
----------------------------- -----------------------------
Blue 0 Bipolar 804541
Yellow 1 CRC Errors 0
Receive Carrier Loss 1 Multiframe Sync 139333
Loss of Sync 1
Both Portmasters are optioned the exact same
The switch type is set to DMS-100 and this has been verified with Sprint to
be the correct switch type. Sprint is complaining about not seeing any
framing coming from my equipment, but I thought the telco was supposed to
provide framing and that was why the Portmaster is showing yellow alarms
(loss of frame). Sprint is also saying that the timing on the line is
slipping and want me to verify I am deriving timing from their line. As far
as I undersatnd it, there is no way to set up a Portmaster other than to
get timing from line0. Any help would be appreciated.
Thanks
-